Estimation of Series Capacitance for a Three-Phase Transformer Winding From Its Measured Frequency Response


Autoria(s): Pramanik, Saurav; Satish, L
Data(s)

2013

Resumo

Recently, authors published a method to indirectly measure series capacitance (C-s) of a single, isolated, uniformly wound transformer winding, from its measured frequency response. The next step was to implement it on an actual three-phase transformer. This task is not as straightforward as it might appear at first glance, since the measured frequency response on a three-phase transformer is influenced by nontested windings and their terminal connections, core, tank, etc. To extract the correct value of C-s from this composite frequency response, the formulation has to be reworked to first identify all significant influences and then include their effects. Initially, the modified method and experimental results on a three-phase transformer (4 MVA, 33 kV/433 V) are presented along with results on the winding considered in isolation (for cross validation). Later, the method is directly implemented on another three-phase unit (3.5 MVA, 13.8 kV/765 V) to show repeatability.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/47748/1/IEEE_Tran_Pow_Del_28-4_2437_2013.pdf

Pramanik, Saurav and Satish, L (2013) Estimation of Series Capacitance for a Three-Phase Transformer Winding From Its Measured Frequency Response. In: IEEE TRANSACTIONS ON POWER DELIVERY, 28 (4). pp. 2437-2444.

Publicador

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

Relação

http://dx.doi.org/10.1109/TPWRD.2013.2260772

http://eprints.iisc.ernet.in/47748/

Palavras-Chave #Electrical Engineering
Tipo

Journal Article

PeerReviewed