Interleaved winding and suppression of natural frequencies


Autoria(s): Pramanik, Saurav; Anees, Sana; Satish, Lakshminarayana
Data(s)

01/04/2013

Resumo

Ideally, it is desirable to design and manufacture a transformer winding that can render all its internal resonances non-excitable. This study examines the effectiveness of an interleaved winding in achieving this goal. While investigating its effectiveness, it led to the establishment of a much desired theoretical basis that reinforces the reasons put forward in the literature to explain internal insulation failures observed in interleaved windings used in extra high voltage (EHV) transformers. Numerical calculations along with experimental verification on actual transformer windings are presented. This study reveals that most of the natural frequencies that are normally non-excitable in the line and neutral current responses of an interleaved winding have been rendered excitable in the disk-to-disk voltages, thus, providing favourable conditions for insulation overstress because of resonant overvoltages. Prevalence of such a condition is an inherent characteristic of interleaved windings.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/47228/1/IET_Elec_Powe_Appl_7-4_237_2013.pdf

Pramanik, Saurav and Anees, Sana and Satish, Lakshminarayana (2013) Interleaved winding and suppression of natural frequencies. In: IET Electric Power Applications, 7 (4). pp. 237-244.

Publicador

Institution of Engineering and Technology-IET

Relação

http://dx.doi.org/10.1049/iet-epa.2012.0362

http://eprints.iisc.ernet.in/47228/

Palavras-Chave #Electrical Engineering
Tipo

Journal Article

PeerReviewed