Realistic minimum desorption temperatures and compressor sizing for activated carbon + HFC 134a adsorption coolers


Autoria(s): Srinivasan, Kandadai; Dutta, Pradip; Saha, Bidyut Baran; Ng, Kim Choon; Prasad, Madhu
Data(s)

2013

Resumo

A low thermal diffusivity of adsorption beds induces a large thermal gradient across cylindrical adsorbers used in adsorption cooling cycles. This reduces the concentration difference across which a thermal compressor operates. Slow adsorption kinetics in conjunction with the void volume effect further diminishes throughputs from those adsorption thermal compressors. The problem can be partially alleviated by increasing the desorption temperatures. The theme of this paper is the determination the minimum desorption temperature required for a given set of evaporating/condensing temperatures for an activated carbon + HFC 134a adsorption cooler. The calculation scheme is validated from experimental data. Results from a parametric analysis covering a range of evaporating/condensing/desorption temperatures are presented. It is found that the overall uptake efficiency and Carnot COP characterize these bounds. A design methodology for adsorber sizing is evolved. (c) 2012 Elsevier Ltd. All rights reserved.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/46390/1/app_the_eng_51_1-2_551_2013.pdf

Srinivasan, Kandadai and Dutta, Pradip and Saha, Bidyut Baran and Ng, Kim Choon and Prasad, Madhu (2013) Realistic minimum desorption temperatures and compressor sizing for activated carbon + HFC 134a adsorption coolers. In: APPLIED THERMAL ENGINEERING, 51 (1-2). pp. 551-559.

Publicador

PERGAMON-ELSEVIER SCIENCE LTD

Relação

http://dx.doi.org/10.1016/j.applthermaleng.2012.09.028

http://eprints.iisc.ernet.in/46390/

Palavras-Chave #Mechanical Engineering
Tipo

Journal Article

PeerReviewed