Natural Frequencies of 3-Pkase Transformer Windings


Autoria(s): Gururaj, BI
Data(s)

01/06/1963

Resumo

Natural frequencies and surge response of the windings of 3-phase transformers have been determined in the past by neglecting the capacitive and inductive couplings between the phase windings. This paper shows that these assumptions are not valid and presents a new method of formulating equivalent networks of 3-phase transformer windings for the various winding connections and terminal conditions. By utilizing these equivalent networks the natural frequencies and surge response of the windings can be determined. Tests made on a model transformer showed good correlation with calculated results.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/43118/1/Natural_frequencies.pdf

Gururaj, BI (1963) Natural Frequencies of 3-Pkase Transformer Windings. In: IEEE Transactions on Power Apparatus and Systems, 82 (66). pp. 318-329.

Publicador

IEEE

Relação

http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=4072800

http://eprints.iisc.ernet.in/43118/

Palavras-Chave #Others
Tipo

Journal Article

PeerReviewed