An Investigation into the Dependence of the Arc Voltage on the Parameters of the Short-Circuit Current and the Design of the Vacuum Interrupter


Autoria(s): Kulkarni, Sandeep; Rajan, Suresh; Andrews, Lalichan; Rajhans, Rupesh; Thomas, Joy M
Data(s)

18/11/2008

Resumo

The vacuum interrupter is extensively employed in the medium voltage switchgear for the interruption of the short-circuit current. The voltage across the arc during current interruption is termed as the arc voltage. The nature and magnitude of this arc voltage is indicative of the performance of the contacts and the vacuum interrupter as a whole. Also, the arc voltage depends on the parameters like the magnitude of short-circuit current, the arcing time, the point of opening of the contacts, the geometry and area of the contacts and the type of magnetic field. This paper investigates the dependency of the arc voltage on some of these parameters. The paper also discusses the usefulness of the arc voltage in diagnosing the performance of the contacts.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/40530/1/An_Investigation.pdf

Kulkarni, Sandeep and Rajan, Suresh and Andrews, Lalichan and Rajhans, Rupesh and Thomas, Joy M (2008) An Investigation into the Dependence of the Arc Voltage on the Parameters of the Short-Circuit Current and the Design of the Vacuum Interrupter. In: 23rd IEEE Intl Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV 2008), 15-19 Sept. 2008 , Bucharest.

Publicador

IEEE

Relação

http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=4676755

http://eprints.iisc.ernet.in/40530/

Palavras-Chave #Electrical Engineering
Tipo

Conference Paper

PeerReviewed