Common mode DC bus filter for Active Front-End converter


Autoria(s): Acharya, BA; John, V
Data(s)

23/12/2010

Resumo

Active Front-End (AFE) converter operation produces electrically noisy DC bus on common mode basis. This results in higher ground current as compared to three phase diode bridge rectifier. Filter topologies for DC bus have to deal problems with switching frequency and harmonic currents. The proposed filter approach reduces common mode voltage and circulates third harmonic current within the system, resulting in minimal ground current injection. The filtering technique, its constrains and design to attenuate common mode voltage and eliminate lower order harmonics injection to ground is discussed. The experimental results for operation of the converter with both SPWM and CSVPWM are presented.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/39075/1/Common_Mode.pdf

Acharya, BA and John, V (2010) Common mode DC bus filter for Active Front-End converter. In: 2010 Joint International Conference on Power Electronics, Drives and Energy Systems (PEDES) & 2010 Power India, 20-23 Dec. 2010, New Delhi.

Publicador

IEEE

Relação

http://ieeexplore.ieee.org/xpls/abs_all.jsp?tp=&arnumber=5712470

http://eprints.iisc.ernet.in/39075/

Palavras-Chave #Electrical Engineering
Tipo

Conference Paper

PeerReviewed