A study of partial discharge characteristics in oil impregnated pressboard insulation
Data(s) |
1996
|
---|---|
Resumo |
An attempt has been made to study the effect of time and test procedure on the behaviour of partial discharge (PD) pulses causing failure of oil-pressboard system under power frequency voltages using circular disc shaped samples and uniform field electrodes. Weibull statistics have been used to handle the large amount of PD data. The PD phenomena has been found to be stress and time dependent. On the basis of stress level, three different regions are identified and in one of the regions, the rate of deterioration of the sample is at a maximum. The work presents some interesting features of Weibull parameters as related to the condition of insulation studied in addition to its usual PD characteristics |
Formato |
application/pdf |
Identificador |
http://eprints.iisc.ernet.in/37039/1/A_Study_of_Partial.pdf Mohsin, MM and Narayanachar, MN and Nema, RS (1996) A study of partial discharge characteristics in oil impregnated pressboard insulation. In: 1996 IEEE International Symposium on Electrical Insulation, JUN 16-19, 1996, MONTREAL, CANADA. |
Publicador |
IEEE |
Relação |
http://ieeexplore.ieee.org/search/srchabstract.jsp?tp=&arnumber=549287&queryText%3DA+study+of+partial+discharge+characteristics+in+oil+impregnated+pressboard+insulation%26openedRefinements%3D*%26searchField%3DSearch+All http://eprints.iisc.ernet.in/37039/ |
Palavras-Chave | #High Voltage Engineering (merged with EE) |
Tipo |
Conference Paper PeerReviewed |