Corona Aging Studies on Silicone Rubber Nanocomposites


Autoria(s): Venkatesulu, B; Thomas, M Joy
Data(s)

01/04/2010

Resumo

In EHV and UHV power transmission lines, corona could occur even on well designed transmission line hardware and insulators especially under wet conditions. Corona if allowed to occur continuously can significantly damage the polymeric insulators used in such lines in the long run. This paper presents the experimental results of corona aging studies conducted on unfilled silicone rubber as well as filled silicone rubber nanocomposites. Corona aging studies were conducted on silicone rubber samples with filler concentrations of 0, 1, 2 and 3 % by wt of nanosilica for 25 h and 50 h. Needle-plane electrode geometry has been used to create the corona on the samples. Different characterization techniques such as Scanning Electron Microscopy, Energy Dispersive X-ray analysis, Hydrophobicity, Fourier Transform Infrared Spectroscopy, and Optical Profilometry have been used to assess the relative performance of the samples with respect to corona aging. Results indicate that at 3 wt %, the performance of the nanocomposite is much better than the unfilled silicon rubber which can be attributed to the modifications in the material caused by the size factor of the filler.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/33142/1/corona.pdf

Venkatesulu, B and Thomas, M Joy (2010) Corona Aging Studies on Silicone Rubber Nanocomposites. In: IEEE Transactions on Dielectrics and Electrical Insulation, 17 (2). pp. 625-634.

Publicador

IEEE

Relação

http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=5448120

http://eprints.iisc.ernet.in/33142/

Palavras-Chave #Electrical Engineering
Tipo

Journal Article

PeerReviewed