An algorithm for optimum control of static VAR compensators to meet phase-wise unbalanced reactive power demands


Autoria(s): Thukaram, D; Iyengar, Ramakrishna BS; Parthasarathy, K
Data(s)

01/10/1986

Resumo

The operation of thyristor-controlled static VAR compensators (SVCs) at various conduction angles can be used advantageously to meet the unablanced reactive power demands in a system. However, such operation introduces harmonic currents into the AC system. This paper presents an algorithm to evaluate an optimum combination of the phase-wise reactive power generations from SVC and balanced reactive power supply from the AC system, based on the defined performance indices, namely, the telephone influence factor (TIF), the total harmonic current factor (IT) and the distortion factor (D). Results of the studies conducted on a typical distribution system are presented and discussed.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/22188/2/1.pdf

Thukaram, D and Iyengar, Ramakrishna BS and Parthasarathy, K (1986) An algorithm for optimum control of static VAR compensators to meet phase-wise unbalanced reactive power demands. In: Electric Power Systems Research, 11 (2). pp. 129-137.

Publicador

Elsevier Science

Relação

http://www.sciencedirect.com/science?_ob=ArticleURL&_udi=B6V30-47XF76Y-1C&_user=512776&_rdoc=1&_fmt=&_orig=search&_sort=d&_docanchor=&view=c&_acct=C000025298&_version=1&_urlVersion=0&_userid=512776&md5=4813579036c65eb3bdbecfb8fcd606af

http://eprints.iisc.ernet.in/22188/

Palavras-Chave #Electrical Engineering
Tipo

Journal Article

PeerReviewed