Evaluating the potential use of direct evaporative cooling in Australia
Data(s) |
01/12/2015
|
---|---|
Resumo |
Greenhouse gas emissions and associated global climate change are a significant and growing concern for the world community. In order to improve building energy efficiency, the use of evaporative cooling systems is attracting growing attention. Using a climate assessment tool, the potential use of direct evaporative coolers over different Australian climates is evaluated. It is found that overall, the potential use of direct evaporative cooling is very significant in Australian climates. Among all the eight capital cities across Australia, except for Darwin, the need of hybrid cooling for other cities is found to be insignificant,and is less than 5% if appropriate air circulation is provided on hot/warm days. It is also found that the potential use of evaporative cooling can be significantly influenced by a change in the applications or design parameters. In Brisbane, it is estimated that with an increase of sensible cooling load from 30 W/m2 to 40 W/m2 in the conditioned space, the requirement in hours of hybrid cooling can increase significantly, from 4.06% to 14.89%. |
Identificador | |
Publicador |
Elsevier B.V. |
Relação |
DOI:10.1016/j.enbuild.2015.09.020 Guan, Lisa, Bennett, Michael, & Bell, John (2015) Evaluating the potential use of direct evaporative cooling in Australia. Energy and Buildings, 108, pp. 185-194. |
Direitos |
Copyright 2015 Elsevier B.V. |
Fonte |
School of Chemistry, Physics & Mechanical Engineering; Science & Engineering Faculty |
Palavras-Chave | #Climate assessment tool #Direct evaporative cooling #Sensitivity study #Design parameters |
Tipo |