Characteristics of the first pre-discharge current pulse in SF6 under a steep fronted impulse voltage


Autoria(s): Nielsen, Shawn D.; Reynders, Jan P.
Data(s)

20/08/2001

Resumo

An improved understanding of the characteristics of the pre-discharge current pulses in GIS will lead to improved analyses of the results from the UHF partial discharge detection method. This paper presents the characteristics of the first pre-discharge current pulses from a point-to-plain geometry at 1 bar absolute under both polarities of a 1.1/80 us lightning impulse. The analysis has shown that the pre-discharge current wave shape, peak current magnitude and charge is effected by the instantaneous voltage at which the pre- discharge took place as well as the polarity of the active electrode. The measured results show that protrusions on the electrodes have slower wave shape parameters than those reported for free conducting particles.

Formato

application/pdf

Identificador

http://eprints.qut.edu.au/86948/

Relação

http://eprints.qut.edu.au/86948/1/4-35.pdf

Nielsen, Shawn D. & Reynders, Jan P. (2001) Characteristics of the first pre-discharge current pulse in SF6 under a steep fronted impulse voltage. In 12th International Symposium on High Voltage, 20-24 August 2001, Bangalore, India.

Direitos

Copyright 2001 [please consult the authors]

Fonte

School of Electrical Engineering & Computer Science; Science & Engineering Faculty

Palavras-Chave #Partial Discharge #SF6 #Impluse #Current Pulse
Tipo