VFT performance of a 180/110 mm co-axial gap in SF6 up to 4 bar absolute
Data(s) |
1999
|
---|---|
Resumo |
Disconnector switch operation in GIS generates VFT voltages in the system. It is important, for insulation co-ordination purposes, to obtain accurate VFT V-t data for typical gap geometries found in GIS. This paper presents experimentally obtained VFT V-t data for a 180/1 lOmm co-axial gap. The VFT has a time to first peak of 35 ns and a oscillation frequency of 13,6 MHz. Due to the location of the voltage divider in a compartment adjacent to the gap, a correction factor of 1.1 is used to relate the measured breakdown voltage to that in the gap. Positive polarity VFT V-t data is presented for 1, 2, 3 and 4 bar absolute and negative polarity VFT data for 3 and 4 bar absolute. Two methods of generating the VFT's are used. The first is to power up the test transformer at power frequency. The second is to generate a switching impulse by discharging a capacitor into the primary of the test transformer. |
Formato |
application/pdf |
Identificador | |
Publicador |
Institution Of Electrical Engineers |
Relação |
http://eprints.qut.edu.au/86676/1/00820379.pdf http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=820379 DOI:10.1049/cp:19990542 Nielsen, Shawn, Jan, Reynders, & Jandrell, Ian (1999) VFT performance of a 180/110 mm co-axial gap in SF6 up to 4 bar absolute. In 11th International Symposium on High-Voltage Engineering (ISH 99), Institution Of Electrical Engineers, Stakis Metropole Hotel, London, United Kingdom, pp. 1-201. |
Direitos |
Copyright 1999 Please consult the author. |
Fonte |
School of Electrical Engineering & Computer Science; Science & Engineering Faculty |
Palavras-Chave | #VFT performance #insulation co-ordination purposes #disconnector switch operation |
Tipo |
Conference Paper |