Fire design rules for load bearing cold-formed steel frame walls exposed to realistic design fire curves


Autoria(s): Ariyanayagam, Anthony Deloge; Mahendran, Mahen
Data(s)

01/10/2015

Resumo

Light gauge Steel Frame (LSF) walls are extensively used in the building industry due to the many advantages they provide over other wall systems. Although LSF walls have been used widely, fire design of LSF walls is based on approximate prescriptive methods based on limited fire tests. Also these fire tests were conducted using the standard fire curve [1] and the applicability of available design rules to realistic design fire curves has not been verified. This paper investigates the accuracy of existing fire design rules in the current cold-formed steel standards and the modifications proposed by previous researchers. Of these the recently developed design rules by Gunalan and Mahendran [2] based on Eurocode 3 Part 1.3 [3] and AS/NZS 4600 [4] for standard fire exposure [1] were investigated in detail to determine their applicability to predict the axial compression strengths and fire resistance ratings of LSF walls exposed to realistic design fire curves. This paper also presents the fire performance results of LSF walls exposed to a range of realistic fire curves obtained using a finite element analysis based parametric study. The results from the parametric study were used to develop a simplified design method based on the critical hot flange temperature to predict the fire resistance ratings of LSF walls exposed to realistic fire curves. Finally, the stud failure times (fire resistance rating) obtained from the fire design rules and the simplified design method were compared with parametric study results for LSF walls lined with single and double plasterboards, and externally insulated with rock fibres under realistic fire curves.

Formato

application/pdf

Identificador

http://eprints.qut.edu.au/86508/

Publicador

Elsevier

Relação

http://eprints.qut.edu.au/86508/1/Full%20Paper.pdf

DOI:10.1016/j.firesaf.2015.05.007

Ariyanayagam, Anthony Deloge & Mahendran, Mahen (2015) Fire design rules for load bearing cold-formed steel frame walls exposed to realistic design fire curves. Fire Safety Journal, 77, pp. 1-20.

Direitos

Copyright 2015 Elsevier

Licensed under the Creative Commons Attribution; Non-Commercial; No-Derivatives 4.0 International. DOI: 10.1016/j.firesaf.2015.05.007

Fonte

School of Civil Engineering & Built Environment; Institute for Future Environments; Science & Engineering Faculty

Palavras-Chave #090502 Construction Engineering #090506 Structural Engineering #090599 Civil Engineering not elsewhere classified #Light gauge steel frame walls #Realistic design fire curves #Axial compression strength of studs #Fire resistance rating #Limiting temperature method #Fire design rules #Simplified design method