Fire performance and design of cold-formed steel wall systems


Autoria(s): Gunalan, Shanmuganathan; Ariyanayagam, Anthony; Mahendran, Mahen
Data(s)

2013

Resumo

Traditionally, the fire resistance rating of Light gauge steel frame (LSF) wall systems is based on approximate prescriptive methods developed using limited fire tests. These fire tests are conducted using standard fire time-temperature curve given in ISO 834. However, in recent times fire has become a major disaster in buildings due to the increase in fire loads as a result of modern furniture and lightweight construction, which make use of thermoplastics materials, synthetic foams and fabrics. Therefore a detailed research study into the performance of load bearing LSF wall systems under both standard and realistic design fires on one side was undertaken to develop improved fire design rules. This study included both full scale fire tests and numerical studies of eight different LSF wall systems conducted for both the standard fire curve and the recently developed realistic design fire curves. The use of previous fire design rules developed for LSF walls subjected to non-uniform elevated temperature distributions based on AISI design manual and Eurocode 3 Parts 1.2 and 1.3 was investigated first. New simplified fire design rules based on AS/NZS 4600, North American Specification and Eurocode 3 Part 1.3 were then proposed with suitable allowances for the interaction effects of compression and bending actions. The importance of considering thermal bowing, magnified thermal bowing and neutral axis shift in the fire design was also investigated and their effects were included. A spread sheet based design tool was developed based on the new design rules to predict the failure load ratio versus time and temperature curves for varying LSF wall configurations. The accuracy of the proposed design rules was verified using the fire test and finite element analysis results for various wall configurations, steel grades, thicknesses and load ratios under both standard and realistic design fire conditions. A simplified method was also proposed to predict the fire resistance rating of LSF walls based on two sets of equations developed for the load ratio-hot flange temperature and the time-temperature relationships. This paper presents the details of this study on LSF wall systems under fire conditions and the results.

Formato

application/pdf

Identificador

http://eprints.qut.edu.au/76347/

Relação

http://eprints.qut.edu.au/76347/2/76347.pdf

Gunalan, Shanmuganathan, Ariyanayagam, Anthony, & Mahendran, Mahen (2013) Fire performance and design of cold-formed steel wall systems. In 4th International Conference on Structural Engineering and Construction Management, 13 - 15 December 2013, Earl's Regency Hotel, Kandy, Sri Lanka.

Direitos

Copyright 2013 Please consult the authors

Fonte

School of Civil Engineering & Built Environment; Science & Engineering Faculty

Palavras-Chave #090506 Structural Engineering #Fire resistance rating #Light gauge steel frame wall systems #Fire tests #Finite element analyses #Fire design rules
Tipo

Conference Paper