Inclusion of PMU current phasor measurements in a power system state estimator


Autoria(s): Chakrabarti, S.; Kyriakides, E.; Ledwich, G.; Ghosh, A.
Data(s)

2010

Resumo

Three different methods of inclusion of current measurements by phasor measurement units (PMUs) in a power sysetm state estimator is investigated. A comprehensive formulation of the hybrid state estimator incorporating conventional, as well as PMU measurements, is presented for each of the three methods. The behaviour of the elements because of the current measurements in the measurement Jacobian matrix is examined for any possible ill-conditioning of the state estimator gain matrix. The performance of the state estimators are compared in terms of the convergence properties and the varian in the estimated states. The IEEE 14-bus and IEEE 300-bus systems are used as test beds for the study.

Identificador

http://eprints.qut.edu.au/41102/

Publicador

The Institution of Engineering and Technology

Relação

DOI:10.1049/iet-gtd.2009.0398

Chakrabarti, S., Kyriakides, E., Ledwich, G., & Ghosh, A. (2010) Inclusion of PMU current phasor measurements in a power system state estimator. IET Generation, Transmission & Distribution, 4(10), pp. 1104-1115.

Fonte

Faculty of Built Environment and Engineering; School of Engineering Systems

Palavras-Chave #090600 ELECTRICAL AND ELECTRONIC ENGINEERING #Jacobian Matrices #Electric Current Measurement #Power System Measurement #Power System State Estimation