Performance study of two different compensating devices in a custom power park
Data(s) |
2005
|
---|---|
Resumo |
Simulation study of a custom power park (CPP) is presented. It is assumed that the park contains unbalanced and nonlinear loads in addition to a sensitive load. Two different types of compensators are used separately to protect the sensitive load against unbalance and distortion caused by the other loads. It has been shown that a shunt compensator can regulate the voltage of the CPP bus, whereas the series compensator can only regulate the sensitive load terminal voltage. Additional issues such as the load transfer through a static transfer switch, detection of sag/fault etc. are also discussed. The concepts are validated through PSCAD/EMTDC simulation studies on a sample distribution system. |
Formato |
application/pdf |
Identificador | |
Publicador |
The Institution of Engineering and Technology |
Relação |
http://eprints.qut.edu.au/37378/1/01467954.pdf DOI:10.1049/ip-gtd:20045014 Ghosh, Arindam (2005) Performance study of two different compensating devices in a custom power park. IET Generation, Transmission and Distribution, 152(4), pp. 521-528. |
Direitos |
Copyright 2005 The Institution of Engineering and Technology |
Fonte |
Faculty of Built Environment and Engineering |
Palavras-Chave | #090600 ELECTRICAL AND ELECTRONIC ENGINEERING |
Tipo |
Journal Article |