Fold back current control and admittance protection scheme for a distribution network containing distributed generators
Data(s) |
2010
|
---|---|
Resumo |
Islanded operation, protection, reclosing and arc extinguishing are some of the challenging issues related to the connection of converter interfaced distributed generators (DGs) into a distribution network. The isolation of upstream faults in grid connected mode and fault detection in islanded mode using overcurrent devices are difficult. In the event of an arc fault, all DGs must be disconnected in order to extinguish the arc. Otherwise, they will continue to feed the fault, thus sustaining the arc. However, the system reliability can be increased by maximising the DG connectivity to the system: therefore, the system protection scheme must ensure that only the faulted segment is removed from the feeder. This is true even in the case of a radial feeder as the DG can be connected at various points along the feeder. In this paper, a new relay scheme is proposed which, along with a novel current control strategy for converter interfaced DGs, can isolate permanent and temporary arc faults. The proposed protection and control scheme can even coordinate with reclosers. The results are validated through PSCAD/EMTDC simulation and MATLAB calculations. |
Identificador | |
Publicador |
The Institution of Engineering and Technology (IET) |
Relação |
DOI:10.1049/iet-gtd.2009.0614 Dewadasa, Manjula, Ghosh, Arindam, & Ledwich, Gerard (2010) Fold back current control and admittance protection scheme for a distribution network containing distributed generators. IET Generation, Transmission & Distribution, 4(8), pp. 952-962. |
Fonte |
School of Engineering Systems |
Palavras-Chave | #090601 Circuits and Systems #090608 Renewable Power and Energy Systems Engineering (excl. Solar Cells) #090699 Electrical and Electronic Engineering not elsewhere classified #Distributed generation #Fold back current control #Admittance relay protection |
Tipo |
Journal Article |